PJM Reviews September Hot Weather Operations

142

PJM and the PJM generation and transmission owners coordinated closely during two unseasonably warm September periods to reliably serve demand while managing tightening generation and transmission system constraints, PJM told the Operating Committee Thursday.

Challenges common to two hot weather periods, Aug. 31 to Sept. 4 and Sept. 15–18, included the need to balance reliability against planned transmission and generation limitations, as well as exports to neighboring systems.

Both occasions also required targeted deployment of Demand Response resources. DOE emergency orders were also used to allow resources that were eligible to continue operating beyond normal operating limits.

During both hot weather periods, PJM also closely coordinated operations and utilized emergency procedures to cover “net load” in the hours immediately after sunset, when the output of solar resources falls faster than electricity use. During these times, generation was also bottled in certain areas because of transmission limitations, particularly resources to serve congested zones in Washington, D.C., Maryland and Virginia.

Shoulder Season Start

Fall shoulder season commences in mid-September when, typically, mild temperatures allow for required, scheduled maintenance and upgrades by generation and transmission owners. As new generation additions continue to be outpaced by rising overall demand, system conditions are tightening.

As a result, PJM operators must coordinate closely with generation and transmission owners and precisely manage those necessary equipment outages during shoulder season in combination with targeted emergency procedures that allow the vital maintenance and construction work to proceed.

 “Ultimately, we have to take these transmission and generation outages, and we can’t simply defer them indefinitely,” Paul Dajewski, PJM Sr. Manager – Dispatch, said Thursday. Generation and transmission outages must occur during the shoulder season to ensure equipment can reliably operate during winter and summer months when electricity demand is high.

Early September Heat

The first hot-spell activity commenced Aug. 31 with a PJM-wide Hot Weather Alert extended through Sept. 4. Peak temperatures in the low to mid 90s affected PJM load areas, even as PJM exports served even hotter conditions in neighboring grids to the south and west.

Effective Sept. 2–8, PJM sought and received a 202c Emergency Order from DOE to allow for the operation of generation subject to operating restrictions. The same order authorized PJM to direct Large Loads to run on emergency backup generation if necessary.

As the event unfolded – just prior to the beginning of the traditional fall maintenance season – generation and transmission outages for this period were at a high of 15,502 MW, or 8.47%, of system capacity on Aug. 31. Peak energy usage during this hot weather event was about 152,800 MW at 5:30 p.m. on Sept. 1.

In addition to the high demand related to hot temperatures,the need for Emergency Procedures was driven by energy exports to neighboring grids (which were also experiencing extreme heat) and transmission and generation constraints.

To handle system stress on Sept. 1, Demand Response resources were called on to reduce electricity demand through the net load peak. This helped to manage transmission constraints that were bottling generation in certain areas.

Demand Response customers are paid in advance to reduce their electricity use during times of system stress.

Late September Hot Weather

Unlike the prior warm weather in September, the heat event Sept. 15–18 arrived as routine transmission and generation maintenance outages were well underway in the shoulder season.

PJM recorded a system peak on Sept. 17 at 4:50 p.m. just shy of 127,000 MW. “There was a lot of customer demand to serve given system conditions,” Dajewski said. He noted system outages of 20.7% of system capacity, or 37,916 MW, on Sept. 18.

For this period, PJM called on Demand Response resources earlier in the operating day. Again, PJM exports helped neighboring grid operators in the South experiencing warmer conditions.